Parameter
Description
TypeReducedNightM
Type of reduced night mode, stop or maintain heating of circuit
ode (CP340)
Parameter linked to
the CP070 parameter
Control strategy
Selection of the control strategy for the zone
(CP780)
Tab.77
Correspondence between the parameters and the circuits
CPxx0 parameters ending in 0 correspond to the CIRCA1 circuit
CPxx1 parameters ending in 1 correspond to the CIRCB1 circuit
CPxx2 parameters ending in 2 correspond to the DHW1 circuit
CPxx3 parameters ending in 3 correspond to the CIRCC1 circuit
CPxx4 parameters ending in 4 correspond to the CIRCAUX1 circuit
Tab.78
Parameters menu
Parameter
Factory setting for each circuit
MaxZoneTFlowS
CIRCA1: Electrical back-up: 50
etpoint
CIRCA1: Hydraulic back-up: 75
(CP000
CIRCB1: Electrical back-up: 50
CP001
DHW1: Electrical back-up: 95
CP002
CIRCC1: Electrical back-up: 50
CP003
CIRCAUX1: Electrical back-up: 95
CP004)
CIRCAUX1: Hydraulic back-up: 75
Zone Function
CIRCA1: Direct
(CP020
CIRCB1: Disable
CP021
DHW1: Disable
CP022
CIRCC1: Disable
CP023
CIRCAUX1: Disable
CP024)
Zone HCZP
CIRCA1: 15
Comfort
CIRCB1: 15
(CP210
DHW1: 15
CP211
CIRCC1: 15
CP212
CIRCAUX1: 15
CP213
CP214)
7756241 - v02 - 19062020
Stop heat demand: heating is deactivated when the room set point tempera­
ture set in the timer programme is below the threshold set in CP070.
Continue heat demand: the heating set point is maintained independently of
the threshold set in CP070.
Automatic
Room Temp. based
Outdoor Temp. based
Outdoor & room based
7.4.2
Installation Setup > CIRCA1/CIRCB1/DHW1/CIRCC1/
CIRCAUX1 > Parameters, counters, signals >
Depending on the installation configuration, only certain circuits are
available. The CIRCA1 \ CIRCB1 \ DHW1 \ CIRCC1 \ CIRCAUX1 circuits
are on the SCB-10 PCB.
Description
Maximum Flow Temperature setpoint zone
For circuit A: Can be set from 7 °C to 100 °C
Functionality of the zone
Disable
Direct
Mixing Circuit
Swimming pool
High Temperature
Fan Convector
DHW tank
Electrical DHW
Time Program
ProcessHeat
DHW Layered
DHW Internal tank
DHW Commercial Tank
DHW FWS EXT
Comfort footpoint of the temperature of heat curve of the circuit
Can be set from 15 °C to 90 °C
set to 15 = the curve base temperature is set automatically and is
the same as the room set point temperature
7 Settings
Factory setting
Stop heat demand
Automatic