DeDietrich MIT-M /E Installation, User And Service Manual page 71

Reversible packaged air source heat pump
Table of Contents

Advertisement

Tab.86
Parameters
Parameter
Description
Cascade
Choice of the leading generator,.AUTO: Switching of order every 7 days
Permutation
Can be set from 0 127
(NP005)
Cascade Type
Cascading boilers by adding successively or in parallel, the boilers function
(NP006)
simultaneously
0 Traditional
1 parallel
CascTOutsideHeat
Outdoor start temperature heating of all stages in parallel mode
Parl (NP007)
Can be set from -10 °C to 20 °C
CascTPostRunGen
Duration of post operation of the cascade generator pump
ePump (NP008)
Can be set from 0 Min to 30 Min
CascInterStageTim
Switch on and switch off timing for the producer of the cascade
e (NP009)
Can be set from 1 Min to 60 Min
CascTOutsideCool
Outdoor start temperature cooling of all stages in parallel mode
Para (NP010)
Can be set from 10 °C to 40 °C
CascadeTypeAlgo
Choice of Cascade Algorithm type, power or temperature
(NP011)
Temperature
Power
CascPowerRiseTi
Cascade, Time to reach Temperature Septoint
me (NP012)
Can be set from 1 to 10
CascForceStop
Force Primary Pump to Stop on cascade
Pprim (NP013)
No
Yes
Cascade Mode
Functionnement Mode of cascade : automatic, heating or cooling
(NP014)
Automatic
Heating
Cooling
Tab.87
Adv. Parameters
ADV parameter
Description of the ADV advanced parameters
NP001
Hysterese high for Producer Manager
Can be set from 0.5 °C to 10 °C
NP002
Hysterese low for Producer Manager
Can be set from 0.5 °C to 10 °C
NP003
Maximum error gain for Producer Manager
Can be set from 0 °C to 10 °C
NP004
Proportional Factor for cascade with Temperature algorithm
Can be set from 0 to 10
7756241 - v02 - 19062020
7 Settings
Factory setting
SCB-10
0
0
10
4
4
30
Temperature
1
No
Automatic
Factory setting
SCB-10
3
3
10
1
MIT-M
71