Air Inlet Temp
IO Processor Temp
Input Power: +5 Volts
Input Power: +12 Volts
Local Power: +2.5 Volts
Local Power: +3.3 Volts
Fan
All Power
All Temp.
Sample Count
value = 1 = 0x1
snc4000 > envMonRangeShow
Air Inlet Temp (C):
Nominal: 5 to 45
Warning: 4 <= N < 5 or 45 < N <= 50
Alarm:
N < 4 or N > 50
IO Processor Temp (C):
Nominal: 5 to 80
Warning: 4 <= N < 5 or 80 < N <= 108
Alarm:
N < 4 or N > 108
Input Power: +5 Volts (V):
Nominal: 4.94 to 5.35
Warning: 4.83 <= N < 4.94 or 5.35 < N <= 5.46
Alarm:
N < 4.83 or N > 5.46
Input Power: +12 Volts (V):
Nominal: 11.62 to 12.62
Warning: 11.50 <= N < 11.62 or 12.62 < N <= 12.87
Alarm:
N < 11.50 or N > 12.87
Local Power: +2.5 Volts (V):
Nominal: 2.40 to 2.58
Warning: 2.36 <= N < 2.40 or 2.58 < N <= 2.62
Alarm:
N < 2.36 or N > 2.62
Local Power: +3.3 Volts (V):
Nominal: 3.20 to 3.39
Warning: 3.13 <= N < 3.20 or 3.39 < N <= 3.46
Alarm:
N < 3.13 or N > 3.46
Fan (RPM):
Nominal: 2520 to 3780
Warning: 2205 <= N < 2520 or 3780 < N <= 4095
Alarm:
N < 2205 or N > 4095
value = 1 = 0x1
envMonRangeShow
The envMonRangeShow command specifies operational ranges for the SNC 4000's environmental
channels. It displays ranges of values associated with the Nominal, Warning, and Alarm states for voltage,
temperature, and fan/blower operation according to the channels defined in the envMonShow command:
SNC 4000 User's Guide
Nominal
27 C
Nominal
30 C
Nominal
5.20 V
Nominal
12.25 V
Nominal
2.48 V
Nominal
3.29 V
Nominal
3245 RPM
Nominal
Nominal
2158
77