v In the "Interval" field, set the time interval to specify how often the
WISE will automatically ping the target. The unit will be second (sec).
vi In the "Failure Condition" field, select the judgment method to check
the Ping IF condition. If you select "Continuous ping failed up to X
times", you can set the continuous failed times with a number between
1 to 60. The Ping status would become failure when the ping action
failed continuously and the failed number exceeds the number you set.
If you select "Attempted X times, failed Y times", WISE would check
the latest X ping results, if the failed number exceeds the number Y, the
Ping status would become failure.
vii User can click the "Ping" button in the "Ping Testing" field to test the
Ping status between the WISE controller and the target.
viii Click on "OK" to confirm the setting and return to the Ping list page.
ix Repeat steps ii~ vi to complete settings of all Pings.
x After you finish all the Ping settings, click "Save" button to save the
settings.