Please note: Do not modify the channel value encoded string when you
are editing the formula. It may cause failures when WISE reads the
channel value.
In addition, click the "Verifying" button could check the result of the
formula.
Please note: Before you click the "Verifying" button, please confirm
that the I/O module setting is saved to WISE if you use the I/O
channels in the formula. Otherwise, the test result would be error
because the I/O module is not found.
viii Click on "OK" to confirm the setting and return to the Internal Register
list page.
ix After return to Internal Register list page, if user want to copy the
settings of a pre-set Internal Register to the new Internal Register,
please click the radio button in front of the pre-set Internal Register and
then click "Copy", a new Internal Register (in sequence) will be added
to the list and the settings of the old Internal Register will be copied to
this newly added Internal Register.
x To remove a pre-set Internal Register, please click the radio button in
front of the pre-set Internal Register and then click "Remove".
xi After all Internal Register settings are completed, click "Save" button
to save the changes.

9.2 Timer Setting

WISE provides "Timer" for timing functions. The Timer status can be
"Stop", "Not Timeout" or "Timeout". They can be included in the IF
Condition statements. The Timer Action can be "Start", "Reset", "Pause" or
"Resume". The Start Action will start to run the Timer and if the Start
Action is triggered one more time when the Timer is running, the Timer will
restart again. The Reset action will reset the Timer and stop running the
Timer. The "Pause" action will pause the Timer counting temporarily. The
"Resume" action is to let the Timer to leave the "Pause" mode, and
continue the Timer counting for the rest second of the Timer.