Figure 28: Rack Rail Kit Parts - Mellanox Technologies Spectrum SN2740 Hardware User Manual

1u switch systems
Hide thumbs Also See for Spectrum SN2740:
Table of Contents

Advertisement

Before mounting the system to the rack, select the way you wish to place the system. Pay atten-
tion to the airflow within the rack cooling, connector and cabling options.
While planning how to place the system, consider the two installation options shown in
Figure
13, and review the following points:
• Make sure the system air flow is compatible with your installation selection. It is import-
ant to keep the airflow within the rack in the same direction.
• Note that the part of the system to which you choose to attach the rails (the front panel
direction, as demonstrated in Option 1 or the FRUs direction, as demonstrated in Option
2) will determine the system's adjustable side. The system's part to which the blades are
attached, will be adjacent to the cabinet.
• In case there are cables that cannot bend within the rack, or in case more space is needed
for cable bending radius, it is possible to recess the connector side or the FRU side by
3.5" (8.9 cm), by optional placement of the system's rails.
• The FRU side is extractable. Mounting the rack blades inverted to the FRU side (Option
2) will allow you to slide the FRUs, in and out.
Rev 2.2

Figure 28: Rack Rail Kit Parts

Mellanox Technologies
Installation
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents