Perform Steps Below in the Order Listed
1.1
Connecting a Shelf to a DSX-1 Cross Connect
References to common, but differing, parameters between the Total Access
3000 and the Total Access 3010, such as number of slots, will be conveyed
by the convention a/b. The "a" represents the Total Access 3000 parameter
and the "b" represents the Total Access 3010 parameter. For example, the
differing number of access slots in the two platforms, 28 for the Total Access
3000 and 22 for the Total Access 3010, would be displayed "28/22."
1.1.1
Introduction
No wire wrapping is necessary for data connections on either the network or loop side
of the Total Access 3000/3010 platform. All the data connections on the shelf itself are
accomplished via eight 64-pin/50-pin AMP connectors that mate with the eight pairs
on the Total Access 3000/3010 backplane. This DLP calls out the pin assignments for
the DSX-side inputs to the Total Access 3000/3010 shelf.
For each AMP connector attached to the Total Access 3000/3010 backplane,
ADTRAN recommends a wire tie be attached on the cable (left) side of the connector.
Wire ties are shipped with the system for customer convenience. Earlier steps in the
installation process encouraged that the wire ties be threaded through the wire tie
anchors mounted on the screw on the left side of each connector prior to reinstalling
the large Plexiglass guard. If the wire ties were not threaded through the anchors
earlier, they can be threaded with the large guard left in place, but it may be faster to
remove the guard. Refer to DLP-701 for details on removal/installation of the guard.
1.1.2
Prerequisite Procedures
The Total Access 3000/3010 shelf should be mounted in its permanent location in the
CO before connecting to the DSX-1 cross connect panel.
1.1.3
Tools and Materials Required
• Small, straight-slot screwdriver
• Wire strippers
• Wire-wrap tool
• Waxed polyester twine
To prevent electrical shock, do not install equipment in a wet location or
during a lightning storm.
Total Access
®
3000/3010 System Manual
TOTAL ACCESS 3000/3010
NOTE
WARNING
6TADLP706-1E
DLP-706
Page 1 of 6
© 2002, ADTRAN, Inc.