6TANTP506-1E
TOTAL ACCESS 3000/3010
NTP-506
Page 4 of 4
2. Allow the unit approximately 60 seconds to completely power up and synchronize
with the SCU. Upon completion, the POWER LED will be flashing yellow,
indicating an Out-of-Service, Unassigned (OOS-UA) state and the Online LED
will be off. The STATUS and OPTICS LEDs will be red and the CLOCK LED
will be yellow.
3. Proceed to DLP-742 for procedure to provision the OC-3 MUX modules.
1.5
Placing the Units in Service
Ensure all alarms are cleared before placing the modules In-Service. This will
prevent false alarms from being transmitted to the network.
1. From the working MUX Menu, select option 2, Provisioning, and press <Enter>.
2. From the Provisioning Menu, select option 1, Service State, and press <Enter>.
3. From the Service State Menu, select option 1, In Service, and press <Enter>.
4. Repeat the above steps for the Protect MUX.
At this point the Power LED on both MUX modules will illuminate green,
indicating an In-Service state. Alarms will also be generated in this state.
MUX A Online LED should be illuminated green and MUX B Online LED
should be off. The Status LED on both MUX units should be green if an OC-3
signal is present and synchronized. If no OC-3 signal is present, both LEDs
will be illuminated red.
© 2002, ADTRAN, Inc.
NOTE
NOTE
Total Access
®
3000/3010 System Manual