Triangle Prevention - ICP DAS USA I-8092F User Manual

2-axis motion control module
Hide thumbs Also See for I-8092F:
Table of Contents

Advertisement

A.3.3 Triangle Prevention
The triangle prevention function prevents a triangle form in linear acceleration fixed
pulse driving even if the number of output plses is low. When the number of pulses that were
utilized at acceleration and deceleration exceeds 1/2 of the total number of output pulses during
acceleration, the IC (MCX312) stops acceleration and enters a constant speed mode. The
triangle prevention function is disabled at resetting. And set the WR6/D3 (AVTRI) bit of the
extension mode by setting command (60h) to 1 can enable the Function.
P=2×(Pa+Pd)
P: Output pulse number
Pa: Number of pulses utilized at acceleration
Pd: Number of pulses utilized at deceleration
ICPDAS
Fig. A-17 Triangle prevention of fixed pulse driving
98
I-8092F Software User Manual

Advertisement

Table of Contents
loading

Table of Contents