Operations; Connecting The Battery Supply - Huawei SmartLi 1.0 User Manual

Hide thumbs Also See for SmartLi 1.0:
Table of Contents

Advertisement

SmartLi 1.0
User Manual

7.1 Connecting the Battery Supply

Prerequisites
Turn on the ready switch on the BCU.
Procedure
Step 1 On the UPS LCD screen:
1.
2.
Step 2 Press and hold the POWER ON/OFF button on the BCU for more than 2s. The
green indicator of the BCU blinks at 4 Hz.
Issue 09 (2023-03-26)
Set System Info > Settings > Battery Settings > Battery Type to Lithium
battery.
NO TICE
– Upgrade the UPS software to the version that supports lithium battery
UPS5000 The Relationship of Software Version to check
connection. See
the version number.
– Thres. of low batt. volt. over dry contact (V/cell): If you set Batt. Volt.
Below Threshold for an output dry contact and the battery voltage is
lower than this threshold, the output dry contact will output signals
accordingly.
Choose System Info > Settings > Dry Contact Set, set MUE07A DI_1 valid-
MUE07A DI_5 valid to Close, and MUE07A DI_1 to MUE07A DI_5 receive dry
contact signals of the fire detection and extinguishing equipment. Set them to
Enable.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7

Operations

7 Operations
93

Advertisement

Table of Contents
loading

Table of Contents