5.1 Powering On Batteries

Prerequisites
Turn on the ready switch on the battery control unit.
Procedure
Step 1 On the UPS LCD screen:
1.
2.
Step 2 Press and hold the POWER ON/OFF button on the battery control unit for more
than 2s. The green indicator of the battery control unit blinks at 4 Hz.
Issue 08 (2022-11-15)
Set System Info > Settings > Battery Settings > Battery Type to Lithium
battery.
NO TICE
– Upgrade the UPS software to the version that supports lithium battery
UPS5000 The Relationship of Software Version to check
connection. See
the version number.
– Thres. of low batt. volt. over dry contact (V/cell): If you set Batt. Volt.
Below Threshold for an output dry contact and the battery voltage is
lower than this threshold, the output dry contact will output signals
accordingly.
Choose System Info > Settings > Dry Contact Set, set MUE07A DI_1 valid-
MUE07A DI_5 valid to Close, and MUE07A DI_1 to MUE07A DI_5 receive dry
contact signals of the fire detection and extinguishing equipment. Set them to
Enable.