Huawei SmartLi 1.0 User Manual page 101

Hide thumbs Also See for SmartLi 1.0:
Table of Contents

Advertisement

SmartLi 1.0
User Manual
● The BCB off alarm is displayed on the UPS LCD and SmartLi LCD. No action is
● After the BCU is started, the green indicator is on for 1s and then off for 4s,
● If multiple SmartLi cabinets are combined, press and hold the POWER ON/OFF
Step 3 Set the language, time, date, network parameters, and system parameters on the
Settings Wizard screen
Figure 7-1 Settings wizard
Step 4 After the green indicator of the BCU blinks at 10 Hz, switch on the battery circuit
breaker on the SmartLi.
● If the green indicator of the BCU blinks at 10 Hz, you cannot cold-start the
● If the green indicator of the BCU blinks at 1 Hz or is steady on, you can cold-
Issue 09 (2023-03-26)
NO TICE
required. After the battery circuit breaker is switched on, the alarm is
automatically cleared.
and the red indicator is steady on.
button on each BCU of the cabinets one by one for more than 2s.
NO TE
In a parallel system, Battery cabinet quantity indicates the total number of battery
cabinets.
NO TICE
UPS.
start the UPS.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Operations
94