Shallow Discharge Test - Huawei SmartLi 1.0 User Manual

Hide thumbs Also See for SmartLi 1.0:
Table of Contents

Advertisement

SmartLi 1.0
User Manual

8.2.1 Shallow Discharge Test

A shallow discharge test is conducted to test the battery loop reliability and short-
time discharge capacity when the batteries have not been discharged for a long
time.
A shallow discharge test can be performed manually or as scheduled. Before
performing a shallow discharge test, ensure that:
1.
2.
3.
4.
Scheduled Shallow Discharge Test
Step 1 On the home screen of the UPS LCD, choose System Info > Settings > Battery
Settings and set Sched. shallow dis. test to Enable.
Step 2 Set Sched. shallow dis. test time and Sched. shallow dis. test interval as
required.
After the setting is complete, the system will perform an automatic shallow
discharge test based on the settings.
----End
Manual Shallow Discharge Test
Step 1 On the home screen of the UPS LCD, choose System Info > Maintenance >
Battery Maint.
Step 2 Tap Start on the right of Shallow Dis. Test to start a shallow discharge test.
----End
Notes for Shallow Discharge Test
Issue 09 (2023-03-26)
NO TICE
The UPS is working in normal mode; float charging or hibernation has lasted
for 2 hours after the SOC reaches 100%; and the load ratio fluctuation is less
than 10%.
The UPS has generated no battery overtemperature, overvoltage, or
overcurrent alarm. No generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm
is generated.
The SmartLi has generated no alarms related to lithium batteries.
When shallow discharge tests are complete, the system records data of the
latest five tests. For details about how to view the test data, see
Test
Data.
The shallow discharge test automatically stops in any of the following cases:
a.
The battery discharge capacity reaches the specified value (10%–50%,
20% by default).
b.
The battery discharge voltage reaches the warning threshold (calculated
in real time by battery management).
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Maintenance
8.3 Viewing
107

Advertisement

Table of Contents
loading