Table 8-2 Product components
No.
Check Item
1
Cabinet
appearance
Issue 09 (2023-03-26)
Acceptance Criteria
There is no air exhaust
vent or refrigerant copper
pipe of the air conditioner
placed above the lithium
battery cabinet, and no
other water leakage risks
exist.
Actual temperature: ______
°C (Allowed temperature:
0°C to 40°C; recommended
temperature: 20°C to 25°C)
Actual humidity: ______%
RH (5%–95% RH, non-
condensing)
Acceptance Criteria
The cabinet is free from
dust (on air filters and
fans), rust, and
deformation.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting: Rectify
the fault based on the
acceptance criteria.
● Check method: Measure
using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
● Check method: Measure
using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting: Rectify
the fault based on the
acceptance criteria.
8 Maintenance
Recommende
d Check
Interval
Monthly
Monthly
Monthly
Recommende
d Check
Interval
Monthly
103