Configuration

3.4 SP Ramp, SP Rate, or SP Programming Set Up Group

Function
Prompt
Lower Display
Single Setpoint Ramp
SP RAMP
Selection
Single Setpoint Ramp
TIME MIN
Time (SP Ramp enabled)
Sinlge Setpoint Final
FINAL SP
Setpoint (SP Ramp
enabled)
Setpoint Rate
SP RATE
Rate Up Value for
EU/HR UP
Loop 1 (SP Rate enabled)
Rate Down Value for
EU/HR DN
Loop 1 (SP Rate enabled)
Setpoint Ramp/Soak
SP PROG*
Programming
*requires SP
Program option
Start Segment Number
STRT SEG
End Segment Number
END SEG
Engineering Units for
RAMPUNIT
Ramp Segments
Number of Program
RECYCLES
Recycles
24

Table 3-3 SP Ramp Function Prompts

Function
Name
If SP Rate and SP Programming are disabled
If SP Ramp and SP Programming are disabled
If SP Ramp and SP Rate are disabled
UDC3300 Basic Model: DC33XB User Manual
Selections or
Range of Setting
Upper Display
DISABL
ENABLE
0 to 255 minutes
Enter a value within the setpoint
limits.
DISABL
ENABLE
0 to 9999
in engineering units per hour
0 to 9999
in engineering units per hour
DISABL
ENABLE
SP PROG must be enabled to
view the remaining prompts.
1 to 11
(odd segment number only)
2 to 12
Always end in a soak segment
(2, 4, ... 12)
TIME (hours.minutes)
EU/MIN (engineering
units/minute)
EU/HR (engineering units/hour)
0 to 99 recycles
Factory
Setting
DISABL
3
1000
DISABL
0
0
DISABL
––
––
TIME
––
12/00