3.11 Control Set Up Group

Introduction
The functions listed in this group deal with how the controller will control the process
including: Number of Tuning Parameter Sets, Setpoint Source, Tracking, Power-up
Recall, Setpoint Limits, Output Direction and Limits, Deadband, and Hysteresis.
Function Prompts

Table 3-11 CONTROL Group Function Prompts

Function Prompt
Lower Display
PV SOURCE
PID SETS
12/04
Selections or
Range of Setting
Upper Display
INPUT 1
INPUT 2
IN ALG1
1 ONLY
2KEYBD
UDC3200 Universal Digital Controller Product Manual
Parameter
Definition
PROCESS VARIABLE SOURCE —Selects the
source of the Process Variable.
INPUT 1
INPUT 2
INPUT ALGORITHM 1
NUMBER OF TUNING PARAMETER SETS—This
selection lets you choose one or two sets of tuning
constants (gain, rate, and reset). NOTE: The
Tuning Group is automatically configured to have
two PID sets when a Duplex Control Algorithm is
configured.
ONE SET ONLY—Only one set of tuning
parameters is available. Configure the values for:
Gain (proportional band),
Rate,
Reset Time, and
Cycle Time (if time proportional is used).
TWO SETS KEYBOARD SELECTABLE—Two sets
of tuning parameters can be configured and can be
selected at the operator interface or by using the
Digital Inputs.
Lower
Lower
Lower
Display
Display
Display
Press this key until you see PID SET1 or PID SET2
then press
or
Configure the values for:
Gain, Rate, Reset, Cycle Time
Gain #2, Rate #2, Reset #2, Cycle #2 Time
Configuration
to switch between sets.
71