Honeywell DC33XB User Manual page 67

Table of Contents

Advertisement

Function
Keyboard Reset
Viewing the
Present Ramp or
Soak Segment
Number and Time
Viewing the
Number of Cycles
Left in the
Program
End Program
Disable Program
12/00
Press
LOWER
until you see
Lower Display: ToBEGN
DISPLAY
Press
LOWER
until you see
Upper Display: "R" and the PV value
DISPLAY
Lower Display: Ramp segments:
# indicates the segment number (Ramp–odd only,
Soak–even only)
XX.XX
until you see
LOWER
Upper Display: "R" and the PV value
DISPLAY
Lower Display: RECYC XX
Number of cycles remaining in the setpoint program.
XX = 0 to 99
When the final segment is completed, the "R" in the upper
display either changes to "H" (if configured for HOLD
state) or disappears (if configured for disable of setpoint
programming).
The controller operates at the last setpoint in the program
in automatic or will be in manual mode at the failsafe
output.
See Section 3.4 for details.
UDC3300 Basic Model: DC33XB User Manual
Setpoint Rate/Ramp/Soak Program Operation
Result
key to reset program to beginning at Hold state.
Soak segments:
Ramp Time – Hours.Minutes
Ramp Rate – EU/MIN or EU/HR
Soak Time – Hours.Minutes
# RA XX.XX
# SK XX.XX
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Udc3300

Table of Contents