Alarms Set Up Group; Table 3-12 Alarms Group Function Prompts - Honeywell DC33XB User Manual

Table of Contents

Advertisement

Configuration

3.13 Alarms Set Up Group

Function
Prompt
Lower Display
A1S1 VAL
Alarm 1, Setpoint 1 Value
Alarm 1, Setpoint 2 Value
A1S2 VAL
A2S1 VAL
Alarm 2, Setpoint 1 Value
Alarm 2, Setpoint 2 Value
A2S2 VAL
A1S1TYPE
Alarm 1, Setpoint 1 Type
A1S2TYPE
Alarm 1, Setpoint 2 Type
Alarm 2, Setpoint 1 Type
A2S1TYPE
A2S2TYPE
Alarm 2, Setpoint 2 Type
Alarm 1, Setpoint 1 State
A1S1 H L
SP Programming Event
A1S1 EV
Alarm State for Alarm 1,
Setpoint 1
A1S2 H L
Alarm 2, Setpoint 1 State
36

Table 3-12 Alarms Group Function Prompts

Function
Name
UDC3300 Basic Model: DC33XB User Manual
Selections or
Range of Setting
Upper Display
Value in Engineering Units
Value in Engineering Units
Value in Engineering Units
Value in Engineering Units
NONE
INP 1
INP 2
PV (Process Variable)
DEV (Deviation)
OUTPUT
SHED
EV ON (Event On – SP
Program)
EV OFF (Event Off – SP
Program)
MANUAL
REM SP (Remote Setpoint)
F SAFE (Failsafe)
PVRATE (PV Rate of Change)
BREAK
Same as A1S1TYPE
Same as A1S1TYPE
Same as A1S1TYPE
LOW
HIGH
BEGIN
END
LOW
HIGH
Factory
Setting
90
10
95
5
NONE
NONE
NONE
NONE
HIGH
- -
LOW
12/00

Advertisement

Table of Contents
loading

This manual is also suitable for:

Udc3300

Table of Contents