Using TUNE at Start-Up for Duplex (Heat/Cool)

Table 4-14 Procedure for Using TUNE at Start-up for Duplex

Step
Heat Zone:
1
• Adjust Local Setpoint 1 to a value within the Heat zone.
• Put the controller in Automatic mode.
• Press the Lower Display and
The output will cycle between 50% and 100% (or high output limit). A large T
appears in the upper display until tuning is completed and final Heat parameters
are entered for PID set 1 in the Tuning group.
2
Cool Zone:
• Adjust Local Setpoint 2 to a value within the Cool zone.
• Put the controller in Automatic mode.
• Press the Lower Display and
The output will cycle between 0 % and 50 % (or low output limit). A large T
appears in the upper display until tuning is completed and final Cool parameters
are entered for PID set 2 in the Tuning group.

4.13 Entering a Security Code

The level of keyboard lockout may be changed in the Set Up mode. However,
knowledge of a security code number (0 to 4095) may be required to change from
one level of lockout to another. When a controller leaves the factory, it has a
security code of 0, which permits changing from one lockout level to another without
entering any other code number.
If you require the use of a security code, select a number from 0001 to 4095 and
enter it when the lockout level is configured as NONE. Thereafter, that selected
number must be used to change the lockout level from something other than NONE.
CAUTION
Write the number on the Configuration Record Sheet in Appendix C so
you will have a permanent record.

Table 4-15 Procedure to Enter a Security Code

Step
Operation
1
Enter Set Up
Mode
2
Select any Set
Up Group
3
Security Code
Entry
52
keys simultaneously to initiate Heat tuning.
keys simultaneously to initiate Cool tuning.
Press
SET UP
Upper Display = SET UP
Lower Display = TUNING
Upper Display = 0
FUNCTION
Lower Display = SECUR
LOOP 1/2
To enter a four digit number in the upper display (0001 to
or
4095)
This will be your security code.