Connecting Can Teamwork Cables - Huawei NetCol5000-C030 User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Figure 4-65 Connecting FE teamwork network cables (multiple units)
----End

4.14.4.3.2 Connecting CAN Teamwork Cables

Context
In CAN networking, one teamwork network supports a maximum of 32 smart
cooling products. If CAN networking is required onsite, set Teamwork CAN
resistor enable on the Teamwork settings page for the first and last smart
cooling products to Yes.
Procedure
Step 1 Prepare an 8-pin standard network cable. The following figure shows the wire
sequence requirements.
Figure 4-66 Wire sequence of the CAN_IN/CAN_OUT network cable
Step 2 Connect the CAN_OUT port of the previous smart cooling product to the CAN_IN
port of the next smart cooling product using a CAN teamwork network cable.
Figure 4-67 Connecting CAN teamwork cables
Issue 06 (2022-12-15)
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
86

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-c032Netcol5000-c065

Table of Contents