Paramete
r
Rotation
Time
High
Temp
Start All
Temp for
HT Start
All
Low Temp
Start All
Temp for
LT Start
All
Step 6 After the setting is complete, tap
----End

4.5 (Optional) Setting Monitoring Parameters

Issue 06 (2022-11-25)
Description
Indicates the time
when rotation takes
place. The value can
be any hour in a day
(0–23).
If this option is
enabled, the cooling
function is enabled
for all smart cooling
products in the
group when the
return air
temperature is
higher than the
Temp for HT Start
All.
-
If this option is
enabled, the heating
function is enabled
for all smart cooling
products in the
group when the
return air
temperature is lower
than the Low Temp
Start All.
-
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
/
The default value is
recommended.
The default value is
recommended.
The default value is
recommended.
The default value is
recommended.
to return to the user menu.
Default Value
00:00
Disable
31°C
Disable
13°C
75