Huawei NetCol8000-A013 User Manual page 108

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
ID
Alarm
607
OutFan1 Speed
Abnormal Alarm
608
OutFan2 Speed
Abnormal Alarm
701
Discharge Press
Sensor Fault
702
Suction Press
Sensor Fault
703
Suction Temp
Sensor Fault
704
Discharge Temp
Sensor Fault
Issue 06 (2022-11-25)
System
Causes
Action
The
1. The outdoor unit is
compressor
shuts down.
2. The outdoor unit is
3. Outdoor fan 1 is
The
1. The outdoor unit is
compressor
shuts down.
2. The outdoor unit is
3. Outdoor fan 2 is
The
1. The pressure sensor
compressor
shuts down.
2. The pressure sensor
The
1. The pressure sensor
compressor
shuts down.
2. The pressure sensor
The
1. The temperature
compressor
shuts down.
2. The temperature
--
1. The temperature
2. The temperature
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
not properly
installed.
in the strong wind
state.
faulty.
not properly
installed.
in the strong wind
state.
faulty.
cable is not properly
connected.
is faulty.
cable is not properly
connected.
is faulty.
sensor cable is not
properly connected.
sensor is faulty.
sensor cable is not
properly connected.
sensor is faulty.
Solution
1. Reinstall the
outdoor unit.
2. Add air baffles.
3. Replace the outdoor
fan 1.
1. Reinstall the
outdoor unit.
2. Add air baffles.
3. Replace the outdoor
fan 2.
1. Check the cables to
the pressure sensor.
2. Maintain or replace
the pressure sensor.
1. Check the cables to
the pressure sensor.
2. Maintain or replace
the pressure sensor.
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
101