Huawei NetCol8000-A013 User Manual page 182

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Menu
Setting > User Menu >
Temp&Humid Setting
Setting > User Menu >
Comm Setting
Setting > User Menu >
Password Setting
Setting > Admin Menu >
Alarm Setting >
Temp&Humid Sensor
Setting > Admin Menu >
Alarm Setting > Compressor
Setting > Admin Menu >
Alarm Setting > Indoor Fan
Issue 06 (2022-11-25)
Name
Temp for HT Start All
Low Temp Start All
Temp for LT Start All
Return Air Temp Set
Return Air Humid Set
Baud Rate
Comm Address
Enable Monitoring Resistor
/
Return Air HT Alarm
Return Air HT Thres
Return Air LT Alarm
Return Air LT Thres
High Humid Alarm
High Humid Thres
Low Humid Alarm
Low Humid Thres
Temp&Humid Alarm Delay
Run Time out Alarm
Run Time out Thres
Start Low Press Mask Time
Run Time out Alarm
Run Time out Thres
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
Hide or 31
24.0°C to 35.0°C
Hide or
Enable/Disable
Disable
Hide or 13
10.0°C to 18.0°C
24.0
The minimum
temperature setting
to the maximum
temperature setting
50.0
The minimum
humidity setting to
the maximum
humidity setting
9600
9600/19200
Setting
1 to 255
No
Yes/No
000001
Six-digit number
Enable
Enable/Disable
32.0°C
25°C to 40.0°C
Enable
Enable/Disable
12.0°C
5°C to 24.0°C
Enable
Enable/Disable
85.0%RH
65.0%RH to
95.0%RH
Enable
Enable/Disable
10.0%RH
5.0%RH to 35.0%RH
60s
5s to 999s
Enable
Enable/Disable
30000h
20000h to 40000h
360s
0 to 600s
Enable
Enable/Disable
50000h
30000h to 80000h
175