Name
Suct Super Heat Set point
Suct Super Heat Dead
zone
Adjust Cycle
P-band
Intergral Time Constant
Diff Time Constant
Ultralow Press Ini Open
Low Press Ini Open
Medium Press Ini Open
High Press Ini Open
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
6.0°C
2.0°C to 20.0°C
2.0°C
0 to 5.0°C
10s
5s to 300s
2.0
0.1 to 10.0
60s
1s to 999s
0
0 to 999s
180step
Min Open to Max
Open
150step
Min Open to Max
Open
120step
Min Open to Max
Open
120step
Min Open to Max
Open