Huawei NetCol8000-A013 User Manual page 42

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Installation Space
Figure 3-6 Space requirements (side pipe routing)
Issue 06 (2022-11-25)
be made of polyethylene film. The paint on the concrete wall and floor must
be moisture-proof.
Incoming outdoor air may increase the load of system heating, cooling,
humidification, and dehumidification. Therefore, it is recommended that
outdoor air be prevented from entering the equipment room. (The incoming
outdoor air should be less than 5% of the entire indoor airflow. All doors and
windows should be closed and the gap should be minimal.)
To ensure the normal operation of the indoor unit, select a spacious space for
installing the indoor unit.
Do not install the indoor unit in a narrow place. Otherwise, the airflow will be
blocked, the cooling period will be shortened, the supply and return air will
mix up, and air noise will be caused.
Do not place the indoor unit in a concave place or at the end of a long and
narrow room.
To facilitate the normal maintenance of the indoor unit, do not install other
devices above the indoor unit.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
35