Optional) Power-Off - Huawei NetCol5000-A035 Quick Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

2. Wizard startup flowchart
When the compressor is 3000 rpm, the following table lists the proper system values.
Ambient
Temperature
< 15°C
15–35°C
35–45°C
> 45°C
13

(Optional) Power-off

1. On the home page, tap Shutdown.
2. Turn off the smart cooling product switch in the upstream PDF.
Precautions
Yes
Select commissioning items
Indoor fan commissioning
Success
Electric heater commissioning
Success
Humidifier commissioning
Success
Condensate pump commissioning
Success
Outdoor fan commissioning
Success
Cooling system commissioning
Success
Proper Discharge Pressure Range
(Running > Device Details >
Compressor)
1.5–2.5 MPa
1.5–3.1 MPa
2.5–3.8 MPa
3.1–4.15 MPa
Start
End
27
No
No
Commissioning
interrupted (Handle
Fail
the fault by referring to
the tips displayed on
Fail
the home screen.
Perform wizard startup
after the handling.)
Fail
Fail
Fail
Fail
Proper Suction Pressure Range
(Running > Device Details >
Compressor)
0.7–1.2 MPa