User Manual (800 mm Width)
Table 3-5 Cable specifications
Scenario
Equipotential
ground cable
Indoor unit
power cable
(optional)
(Optional)
Outdoor unit
power cable
(Optional)
Signal cable for
indoor and
outdoor units

3.3 Layout Requirements

3.3.1 Indoor Unit Space Requirements

Equipment Room Requirements
Issue 06 (2022-11-25)
Specifications
2
6 mm
Electrical power cable, 600 V/1000 V,
ZA-RVV, 5 x 6 mm
wires), 46 A, outdoor cable, CE
Naked crimping terminal: OT, 6 mm
M6, 50 A, tin plating, 12–8 AWG
Electrical power cable, 600 V/1000 V,
ZA-RVV, 3 x 6 mm
wires), 46 A, outdoor cable, CE
Naked crimping terminal: OT, 6 mm
M6, 50 A, tin plating, 12–8 AWG
Electrical power cable, 300 V, SJTW, 3 x
16 AWG, black (three cores), 10 A,
shielded outdoor cable, UL
Naked crimping terminal, single cord
end terminal, 1.5 mm
To ensure that the environment control system in the smart cooling product
room works properly, take moisture-proof and thermal insulation measures.
Ensure that the equipment room provides good heat insulation and has
moisture-proof layers. The moisture-proof layer of the ceiling and wall must
Copyright © Huawei Technologies Co., Ltd.
outdoor copper cable
2
, black (five core
2
, black (three core
2
, 16 A, red
3 Installation
Description
The length is
determined based
on site survey.
The cable should
not be lighter than
the common PVC-
sheathed flexible
cable (cable 53 in
IEC 60227). The
length of the cable
is determined by
the site survey.
Delivered with the
2
,
device
The cable should
not be lighter than
the Neoprene
armored flexible
cable (cable 57 in
IEC 60245). The
length of the cable
is determined by
the site survey.
Delivered with the
2
,
device
The length is
determined based
on site survey.
Delivered with the
device
34