Layout Principles - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Figure 3-11 Space requirements for installing multiple outdoor units

3.4 Layout Principles

The layout principles are as follows:
● The height deviation refers to the distance between the stop valve of the
indoor unit and that of the outdoor unit.
● In the figure,
is at least 1:200. The pipe tilting direction should be consistent with the
hypotenuse of the right triangle.
Issue 06 (2022-11-25)
If the outdoor unit is placed higher than the indoor unit, the maximum height
deviation between them should be less than or equal to 20 m. An oil trap
should be installed every 5 m to 6 m in the vertical direction along the gas
pipe to ensure system reliability.
If the indoor unit is placed higher than the outdoor unit, the maximum height
deviation between them should be less than or equal to 5 m.
NO TICE
is a sign of a tilt, indicating that the scale of the pipe tilting
Copyright © Huawei Technologies Co., Ltd.
3 Installation
38