Huawei NetCol8000-A013 User Manual page 29

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Altitu
de
(m)
Coolin
g
capaci
ty
coeffic
ient
Note: The sensible heat ratio under rated working conditions is always 100%.
Installation Requirements
Table 2-4 Installation requirements
Item
Room
door
Floor
Equivale
nt
length
of the
one-
way
pipe
Height
differen
ce
betwee
n indoor
and
outdoor
units
Issue 06 (2022-11-25)
0
1000
1500
1
0.940
0.909
Specifications
Width ≥ 1.2 m; height ≥ 2.3 m
Floor bearing capacity ≥ 350 kg/m
≤ 60 m
● If the outdoor unit is placed higher than the indoor unit, the
maximum vertical distance between them is 20 m.
● If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 m.
Copyright © Huawei Technologies Co., Ltd.
2000
2500
3000
0.878
0.846
0.815
2
2 Overview
3500
4000
0.784
0.753
22