Huawei NetCol8000-A013 User Manual page 112

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
ID
Alarm
716
Power Underfreq
Alarm
717
Group Unit Qty
Mismatch Alarm
718
Teamwork
Network Fail
Alarm
719
InUnit EEPROM
Alarm
Issue 06 (2022-11-25)
System
Causes
Action
The system
1. The power supply
shuts down all
components.
2. The power supply
3. The transformer 2 is
4. The indoor unit
5. The outdoor unit
--
1. One slave unit in
2. The teamwork
3. The number of units
--
1. The master unit is
2. The teamwork
3. The master unit and
--
The EEUROM of the
main control board of
the indoor unit is
faulty.
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
frequency of the
indoor unit is too
low.
frequency of the
outdoor unit is too
low.
faulty.
main control board
is faulty.
main control board
is faulty.
the teamwork group
powers off.
connection fails.
is incorrectly set for
the master unit in
the teamwork
group.
powered off.
connection fails.
a slave unit have
the same address.
Solution
1. Spot-check the
power supply
frequency of the
indoor unit and
increase the power
supply frequency of
the indoor unit.
2. Spot-check the
power supply
frequency of the
outdoor unit and
increase the power
supply frequency of
the outdoor unit.
3. Replace the
transformer 2.
4. Replace the main
control board of the
indoor unit.
5. Replace the main
control board of the
outdoor unit.
1. Check the slave unit
that has powered
off and power it on.
2. Check and re-detect
the teamwork
connection.
3. Check the number
of units and set it
correctly.
1. Check the master
unit that has
powered off and
power it on.
2. Check and re-detect
the teamwork
connection.
3. Check and set the
correct address.
Replace the main
control board of the
indoor unit.
105

Advertisement

Table of Contents
loading