Huawei NetCol8000-A013 User Manual page 102

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
ID
Alarm
216
Comp Drive
Overheat Alarm
217
Comp Drive
Alarm
Issue 06 (2022-11-25)
System
Causes
Action
The
Protection against
compressor
overheating of the
shuts down.
compressor drive board
is triggered.
The
The compressor drive
compressor
board of the outdoor
shuts down.
unit is faulty.
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
Solution
1. Check whether the
fan speed of the
outdoor unit is
normal.
2. Check whether
refrigerant in the
system is
insufficient, which
causes the low
speed of the
outdoor unit fan.
3. Check the
installation
environment of the
outdoor unit to see
whether the heat
dissipation of the
outdoor unit is poor
and whether the
outdoor unit is
blocked.
4. Check whether the
fins of the outdoor
unit are polluted,
which causes the air
intake volume of
the outdoor unit to
be small.
1. Check the
compressor status.
2. Check the
connections
between the
compressor and the
drive board.
3. Check the status of
the compressor
drive board.
4. Replace the
compressor drive
board or
compressor.
95