NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Menu
Setting > Admin Menu >
System Setting >
Temp&Humid Sensor
Setting > Admin Menu >
System Setting >
Compressor
Issue 06 (2022-11-25)
Name
Dehumtemp Comp
Dehum Comp On Demand
Dehum Comp Off Demand
Max Temp Set
Min Temp Set
Max Humid Set
Min Humid Set
Temp P-band
Temp Deadzone
Dehum P-band
Dehum Dead zone
Humid P-band
Humid Dead zone
Min Run Time
Min Stop Time
Min Speed
Max Speed
Oil Return Cycle
Forced Oil Return Cycle
Oil Return Speed
Stop Vacuum Speed
Stop Vacuum Pressure
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
Enable
Enable/Disable
0%
–50 to +50%
50%
0 to 100%
32.0
18°C to 35°C
18.0
18°C to 35°C
90.0%RH
20.0%RH to
100.0%RH
30.0%RH
20.0%RH to
70.0%RH
3.0°C
0.5°C to 20.0°C
1.0°C
0.1°C to 20.0°C
5.0%
1.0% to 90.0%
1.0%
0.5% to 90.0%
5.0%
1.0% to 90.0%
1.0%
0.5% to 90.0%
180s
120s to 600s
180s
120s to 600s
1200rpm
1200 rpm to 4800
rpm
4800rpm
1200 rpm to 4800
rpm
180s
120s to 600s
2h
2h to 24h
3000rpm
From Min Speed to
Max Speed
1800rpm
From Min Speed to
Max Speed
0.48 MPa
0 to 1.5 MPa
177