Device Power-On - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
No.
8
9

4.2 Device Power-On

Prerequisites
Context
● Parameters under the administrator menu can be modified only by certified
technical personnel. Unauthorized modification may cause the smart cooling
product to work abnormally or even be damaged. The involved party shall be
liable for any damage caused thereby.
● For system security purposes, change the preset password after first login.
● The preset passwords for the setting and maintenance menus are as follows.
Issue 06 (2022-11-25)
Icon
Name
Left
Right
NO TE
If you press and hold the
for 5s, a prompt tone is generated, and the password and all parameters are restored to
factory settings. For example, the system configuration and communication configuration
parameters are restored to factory settings, and the user password, the administrator
password, and the maintenance password are also restored to the preset password 000001.
Check that the cables of the indoor and outdoor units are correctly connected
and that the input voltage meets requirements.
Ensure that the smart cooling product circuit breaker in the upstream power
distribution frame (PDF) is OFF.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Function Description
● On a menu screen, press this key to access the
previous screen.
● On the screen for entering a password, press
this key to move the cursor leftward.
● On a menu screen, press this key to access the
next screen.
● On the screen for entering a password, press
this key to move the cursor rightward.
,
,
, and
4 Power-On Commissioning
buttons at the same time
67

Advertisement

Table of Contents
loading

Table of Contents