NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Context
● Move the outdoor unit close to the installation position before unpacking. You
are advised to keep the outdoor unit vertical during transportation. If tilt is not
avoidable, the tilt angle cannot exceed 15°.
● Do not hold the fan guard on the enclosure. Otherwise, it will be deformed.
● Do not touch the blades with hands or other objects.
● After installing the outdoor unit, remove the protective cardboard from
condenser fins.
Procedure
Step 1 Determine the four mounting holes of the outdoor unit based on the installation
dimensions and drill holes in the concrete groundwork.
Step 2 Align the outdoor unit mounting holes with the holes in the concrete base, and
secure the outdoor unit to the concrete base using four M10 expansion bolts, as
shown in
Figure 3-21 Installing an outdoor unit
----End
Issue 06 (2022-11-25)
NO TICE
Figure
3-21.
Copyright © Huawei Technologies Co., Ltd.
3 Installation