Huawei NetCol8000-A013 User Manual page 98

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
ID
Alarm
207
Comp LP Switch
Alarm
208
Comp LP Switch
Lock Alarm
Issue 06 (2022-11-25)
System
Causes
Action
The
1. The condenser fins
compressor
shuts down.
2. The indoor fan or its
3. The cables to the
4. The low pressure
5. The liquid solenoid
6. Refrigerant leaks.
7. The indoor unit is
8. The EEV is faulty.
9. The stop valve is not
10.The filter dryer is
11.The selected model
12.The connecting pipe
The
The Comp LP Switch
compressor
Alarm is triggered
shuts down.
multiple times within a
(The alarm
specified period of
needs to be
time.
manually
cleared.)
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
are dirty or blocked.
drive is faulty.
low pressure switch
are loose or
damaged.
switch is faulty.
valve is faulty.
not properly
installed.
fully open.
dirty or blocked.
is incorrect.
is bent.
Solution
1. Clean the
evaporator fins.
2. Maintain or replace
the indoor fan drive
or indoor fan.
3. Check the cables to
the low pressure
switch.
4. Maintain or replace
the low pressure
switch.
5. Maintain or replace
the solenoid valve
coil or the solenoid
valve.
6. Identify and repair
the leaking point,
and refill refrigerant
after maintenance.
7. Reinstall the indoor
unit.
8. Maintain or replace
the EEV coil or EEV.
9. Check and fully
open the stop valve.
10.Check and replace
the dryer.
11.Check that the
selected model is
correct.
12.Check and replace
the connecting pipe.
Refer to the solution to
the Comp LP Switch
Alarm.