Issue 06 (2022-11-25)
Name
Fan1 Run time out Alarm
Fan1 Run time out Thres
Fan2 Run time out Alarm
Fan2 Run time out Thres
Undervolt Thres
Overvolt Thres
Over Freq Thres
Under Freq Thres
Air Filter RT out Alarm
Air Filter RT out Alarm
Smoke Sensor Alarm
Floor Water Alarm
Fire Alarm
Run Time out Alarm
Run Time out Thres
Humid RT out Alarm
Humid RT out Thres
Pump RT out Alarm
Pump RT out Thres
Delete All Historical
Alarms
Forced Cooling
Dehumidifying
Humidifying
Heating
Freq Rise Temp Demand
Freq Drop Temp Demand
Heating Temp Demand
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
Enable
Enable/Disable
40000h
30000h to 80000h
Enable
Enable/Disable
40000h
30000h to 80000h
85%
83% to 100% (220V)
110%
100% to 112%
(240V)
63Hz
61Hz to 63Hz
47Hz
47Hz to 49Hz
Enable
Enable/Disable
4320h
2160h to 6480h
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
30000
20000h to 40000h
Enable
Enable/Disable
8760h
4380h to 17520h
Enable
Enable/Disable
40000h
10000h to 50000h
No
Yes/No
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
50%
0% to 100%
–50%
–100% to 0%
–100%
–100% to 0%