Huawei NetCol8000-A013 User Manual page 185

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Menu
Setting > Admin Menu >
System Setting > Indoor Fan
Setting > Admin Menu >
System Setting > Outdoor
Fan
Setting > Admin Menu >
System Setting > EEV
Issue 06 (2022-11-25)
Name
Comp Preheating
Dis HT Rise Limit Temp
Dis HT Drop Temp
Min Speed
Max Speed
Dehumid Speed
Min S/R Air Temp Diff
Max S/R Air Temp Diff
Start Delay
Stop Delay
Min Speed
Max Speed
Min Run Pressure
Start Pressure
Max Run Pressure
Min Open
Max Open
Standby Open
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
On (The
On/Off
default
value is On
for the first
startup and
the value is
Off after
preheating
is
complete.)
97.0°C
90°C to 115°C
107.0°C
90°C to 115°C
30%
30% to 100%
100%
30% to 100%
80%
Minimum value:
(Maximum speed of
the indoor fan –
30%) or minimum
speed of the indoor
fan, take the smaller
value
Maximum value:
maximum speed of
the indoor fan
5.0°C
1.0°C to 20.0°C
10.0°C
1.0°C to 20.0°C
30s
0 to 99s
30s
0 to 99s
27.5%
20% to 40%
100%
40% to 100%
2.10 MPa
1.0 MPa to 3.5 MPa
2.26 MPa
1.0 MPa to 3.5 MPa
2.80 MPa
2.5 MPa to 4.0 MPa
52step
0 to 480 step
480step
0 to 480 step
300step
Min Open to Max
Open