Setting Communications Parameters (Snmp Parameters) - Huawei NetCol5000-A User Manual

42 kw air cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-A:
Table of Contents

Advertisement

NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
Parameter
Client
encrypt
Server
encrypt
Network IP
Network
port
----End

4.5.7 Setting Communications Parameters (SNMP Parameters)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings.
displayed.
Issue 01 (2017-07-27)
Setting
Enable,
Disable
Enable,
Disable
N/A
N/A
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section. They will be used when you access a precision
air conditioner to an EMS (element management system).
One precision air conditioner supports concurrent access of up to 10 EMSs through
SNMP.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Setting Method
a client, can connect to a remote server and establish
communication.
If you set Link mode to Server and client, the air
conditioner, as a server, supports two client
connection and establishes communication. In
addition, the air conditioner, as a client, can connect to
a remote server and establish communication.
The default value is Enable. This parameter is
configurable when Link mode is set to Client.
The default value is Disable. This parameter is
configurable when Link mode is set to Server.
Enter the actual IP address of the EMS. IP addresses of
the display panel, EMS client, and EMS server must be
unique. This parameter is configurable when Link mode
is set to Client.
It is recommended that you retain the default value
16100. If you need to change the value, enter a value as
required. This parameter is configurable when Link
mode is set to Client.
4 Commissioning
Figure 4-15
is
103