3.2.3 Installation Layout Principles
Layout principles for installing the NetCol5000-A are as follows:
Issue 01 (2017-07-27)
Item
Specifications
Water
Electrical power cable, 5 m, 22
detection
AWG, black, (2 x T0.5
cable
x 22UL1007, black), (2 x T0.5
orange)
If the outdoor unit is placed higher than the indoor unit, the vertical distance between
them should be less than or equal to 30 m. An oil trap should be installed every 5 m to 6
m in the vertical direction along the gas pipe to ensure system reliability.
(Optional) Pipe Assembly
specifications.
If the indoor unit is placed higher than the outdoor unit, the vertical distance between
them should be less than or equal to 8 m.