2.6 Environment requirements

Table 2-2
Table 2-2 Environment requirements
Item
Product model
Environment
Operating temperature
Operating humidity
Altitude
Storage temperature
Storage humidity
Water requirements
Maximum water
temperature

2.7 Technical Specifications

Table 2-3
Table 2-3 Technical specifications of the NetCol5000-C030H2A2010020E0
Item
Category
Cooling mode
Cooling capacity
Rating power
Air supply mode
Power supply
Fan characteristic
Issue 02 (2013-12-10)
describes the environment requirements for the NetCol5000-C.
1:When the ambient temperature is below 0 ° C, the NetCol5000-C need to increase certain
concentration of ethylene glycol solution, specifically refer to
Glycol Correction Coefficient Curves.
lists the technical specifications of the NetCol5000-C.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Environment Requirements
NetCol5000-C030H2A2010020E0
Class A environment in data centers
1
4 ° C to 55 ° C
≤ 95% RH
Less than 1000 m. If the altitude exceeds 1000 m, the cooling
capacity decreases by 7% to 9% for every additional 1000 m.
-40 ° C to +70 ° C
≤ 95% RH
Filter need to be installed on the inlet pipe, PH value of chilled
water is 7.0 ~ 9.0
20° C
Description
Chilled water-cooled in-row precision air conditioner
Chilled water cooled
1
30 kW
1 kW
Horizontal air supply
200 V to 240 V 1 Ph 50/60 Hz
EC fan