What is the TruVu™ ChillerVu™ Plant Controller?
The TV-PSM has 4 physical ports for BACnet or Modbus communication:
Port
Port type
Gig-E
10/100/1000 Mbps Ethernet
S1
High-speed EIA-485 port
S2
Electrically isolated EIA-485 port
Service
10/100 Mbps Ethernet
Port
HTTP/IP
NOTE The TV-PSM does not support CCN networks.
The TV-PSM also has the following ports:
I/O Bus port for wired TruVu
I/O bus edge connector for directly-connected TruVu
Xnet port for MPC Open XPIO expanders
Rnet port for ZS sensors, Wireless Adapter for wireless sensors, and an Equipment Touch
USB port for recovery
Ethernet Service Port for connecting locally to controller setup pages and the TruVu™ ET Display

Critical Product Announcement

Due to the global semiconductor supply chain uncertainty, the TV-PSM does not yet support communication over
the ARCNET network. References to ARCNET in this document are for future use and should be ignored at this
time.
The TV-PSM's driver properties and controller setup pages only show available communication selection options.
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
For routing this type
of communication...
BACnet/IP,
BACnet/Ethernet, and/or
Modbus TCP/IP
BACnet/ARCNET
or
BACnet/MSTP
or
Modbus Serial
BACnet/MSTP
or
Modbus Serial
BACnet/IP Service Port
TM
MPC I/O expanders
TM
2
At...
10, 100, or 1000 Mbps
(1 Gbps)
156 kbps
9.6 to 115.2 kbps
9.6 to 115.2 kbps
9.6 to 115.2 Kbps
9.6 to 115.2 kbps
10 or 100 Mbps
MPC I/O expanders