TruVu™ UCXP683T
Installation and Start-up Guide
Carrier ©2022 · Catalog No. 11-808-851-01 · 5/10/2022

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TruVu UCXP683T and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier TruVu UCXP683T

  • Page 1 TruVu™ UCXP683T Installation and Start-up Guide Carrier ©2022 · Catalog No. 11-808-851-01 · 5/10/2022...
  • Page 2 Verify that you have the most current version of this document from www.hvacpartners.com, the Carrier Partner Community website, or your local Carrier office. Important changes are listed in Document revision history at the end of this document. Carrier ©2022. All rights reserved.
  • Page 3: Table Of Contents

    Contents What is the TV-UCXP683T? ............................1 Specifications ................................ 2 Zone sensors ................................. 6 Touchscreen devices ............................6 To mount the TV-UCXP683T............................7 Wiring for power ................................8 To wire for power ..............................8 Addressing the TV-UCXP683T through the Service port ................... 9 To set the IP address ..............................
  • Page 4 Contents Device tab ................................47 Ports tab ................................47 BACnet tab ................................48 Modbus tab ................................. 48 Security tab ................................. 48 Local Network tab .............................. 48 To communicate through the BACnet/Service port network ................. 52 To communicate locally through the Rnet port....................... 54 To set up a Local Access connection in the i-Vu®...
  • Page 5: What Is The Tv-Ucxp683T

    Provides 8 universal inputs, 6 binary outputs, 2 analog outputs, and 1 universal output • The universal output can be configured as binary, analog, or pulse-width modulated analog • Supports I/O expanders (future use) TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 6: Specifications

    Rnet port for connecting ZS sensors, an Equipment Touch, an TruVu™ ET Display, and Wireless Adapter for wireless sensors • Service USB port for connecting locally to controller setup pages, the TruVu™ ET Display, or the Carrier wireless service adapter •...
  • Page 7 Use an external transformer if your devices exceed the maximum power. Service port USB 2.0 host port for setting up the controller and troubleshooting through a local connection to a computer, connecting to the TruVu™ ET Display, or the Carrier wireless service adapter. Comm port For future use.
  • Page 8 Tx (Transmit) and Rx (Receive) activity LED and yellow link status LED for the following ports: Ethernet port Eth0 ○ Ethernet port Eth1 ○ • Output LEDs indicate status of each binary output. • Prog LED is customizable. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 9 Listed UL 916, PAZX7, Energy Management Equipment Europe: Mark, UK: EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment RoHS Compliant: 2015/863/EU REACH Compliant TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 10: Zone Sensors

    • The TruVu™ ET Display requires a 24 Vdc external power source. CAUTION A touchscreen device can share a power supply with the Carrier controller if: • The power source shared by the controller and Equipment Touch is AC power.
  • Page 11: To Mount The Tv-Ucxp683T

    Use flat washers to prevent the screw head from deforming the plastic. 7.78 in. (19.77 cm) 5.88 in. (14.94 cm) 5.3 in. (13.45 cm) 4.50 in. (11.43 cm) Depth: 2.00 in (5.08 cm) TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 12: Wiring For Power

    The TV-UCXP683T is powered by a Class 2 power source. Take appropriate isolation measures when mounting it in a control panel where non-Class 2 circuits are present. • Carrier controllers can share a power supply as long as you: • Maintain the same polarity.
  • Page 13: Addressing The Tv-Ucxp683T Through The Service Port

    Local Network tab (page 13) and the Local Network (page 48) tab. You can connect the TV-UCXP683T to a computer using either the Carrier wireless service adapter or a USB cable. NOTE You cannot access the Service port by plugging an Ethernet cable into Eth0 or Eth1.
  • Page 14 Open a web browser on the computer Navigate to http://local.access or http://169.254.1.1 to see the controller setup pages. See To set up the controller through the Service Port (page 46) for detailed information. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 15: To Set The Ip Address

    On the controller setup Ports tab under IP Port, select Custom Static. Enter the IP Address, Subnet Mask, and Default Gateway addresses that the network administrator gave you. Click Save. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 16: To Set The Port S1 Address And Baud Rate

    Autobaud does not work unless there is a device on the network, whether Carrier or third party, that has the baud rate already set. You can manually set the baud rate on more than one device, as long as the rate is the same for every device.
  • Page 17: Addressing A Network Of Controllers Using The Controller Setup Local Network Tab

    Network tab You can use the controller setup Local Network tab to discover Carrier i-Vu® XT or TruVu™ devices on a single network. You can configure them and assign addresses to each one using one of the methods described below.
  • Page 18: Method 2: To Address When You Do Not Know The Serial Numbers

    One technician alone can address the controllers on a mobile device showing the Local Network page by plugging the Carrier wireless service adapter into a controller's Service Port. Then, with the computer, move to each controller within 100 ft. of the adapter. Pressing the DSC button on the controller displays a blue dot in the table where the addressing information can be entered.
  • Page 19: Wiring For Communications

    See Wiring devices to the TV-UCXP683T's Act Net port (page 19). Default for MS/TP is 76.8 kbps. Default for Modbus is 38.4 kbps. See To set up the controller through the Service port (page 46). TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 20: Wiring Specifications

    BACnet Broadcast Management Device (BBMD). Do not configure more than one BBMD per subnet as this may cause circular routes. See "Setting up BACnet Broadcast Management Devices (BBMDs)" in SiteBuilder or i-Vu® Help. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 21: To Wire To A Bacnet Ms/Tp Network

    BACnet: You can wire a third-party BACnet device to the TV-UCXP683T's Eth0, Eth1 port or Port S1. See the BACnet Integration Guide for the TV-UCXP683T. Modbus: You can wire a third-party Modbus master or slave device to Port S1. See Modbus Integration Guide for the TV-UCXP683T. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 22: Wiring Devices To The Tv-Ucxp683T's Rnet Port

    See the device's Installation and Start-up Guide for complete wiring instructions. NOTES • ZS sensors, a Wireless Adapter, and an Equipment Touch can share the same Rnet. • The Rnet communicates at a rate of 115.2 kbps. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 23: Wiring Devices To The Tv-Ucxp683T's Act Net Port

    Wiring devices to the TV-UCXP683T's Act Net port Supports a combination of up to 5 Act Net addresses, as follows: • Address 1 is reserved for the Carrier actuator • Address 2 and 3 are reserved for the VAV Zone II Secondary Duct •...
  • Page 24 (91.44 meters). The bus should be wired with copper conductors of an appropriate size (18 AWG or larger) to compensate for voltage drop and ensure that bus voltage does not drop below 19.2 Vac or 21.6 Vdc. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 25: Wiring Inputs And Outputs

    Each relay can switch up to 3.75 A, 30 Vac/Vdc. The total power and current that can be switched by a bank of 3 relays cannot exceed the Class 2 limits of 100 VA or 4.2 A. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 26: Wiring Specifications

    Acceptable voltage drop in the wire from the controller to the controlled device • Resistance (Ohms) of the chosen wire gauge • Maximum current (Amps) the controlled device requires to operate TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 27: To Wire Inputs And Outputs

    The Gnd terminal is shared by the inputs/outputs to the right and left of it. The TV-UCXP683T has connections for two separate busses. Verify that the TV-UCXP683T's power and communications connections work properly. Turn off the TV-UCXP683T's power. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 28 UO-01 (+) and Common (–) terminals before setting the DIP switch to Analog. Do not apply voltage to the universal output if the DIP switch is set to Analog. ○ TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 29 Wiring inputs and outputs Connect binary and analog output wiring to the screw terminals on the TV-UCXP683T and to the controlled device. Connect the ground wire to the AO outputs' terminals. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 30 See Troubleshooting inputs and outputs (page 59). NOTE You can install connector covers (sold separately, part #PLM-KIT) by snapping them over the terminal block sections on the top and bottom of the controller. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 31: To Adjust Input And Output Properties

    To verify each output's operation, lock each output to a known condition on the I/O Points tab, then verify that the equipment operates correctly. See Troubleshooting inputs and outputs (page 59). TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 32: Input Values

    You can set up a custom translation table on the driver's Custom Translation Tables pages in the i-Vu® interface. The control program must have one Pulse to Analog Input microblock for each pulse counting input. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 33: Output Values

    0–10 Vdc actuator so that when the PID signal is 100%, the TV-UCXP683T output is 10 Vdc. Similarly, when the PID signal is 50%, the TV-UCXP683T output is 5 Vdc. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 34: Resolution Values

    When the control program's signal to the microblock is on, if Polarity is set to: normal—output is on reversed—output is off NOTE Regardless of Polarity, the output will be off if the TV-UCXP683T loses power. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 35: Find And Upload In The I-Vu® Interface

    When complete, a check mark under Status indicates a successful upload. NOTES If an error message appears, click on the message to view an explanation. ○ For details, see the i-Vu® Help. ○ TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 36: Adjusting The Tv-Ucxp683T Driver Properties

    If unsuccessful, the indicate failure point will transition to an idle state for 30 seconds before attempting to communicate again. Change this field only if directed by Technical Support. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 37 You can unlock a device for 24 hours to make IP address changes. Configuration from other devices on the local network for 24 hours Debug Enable Debug Messages Enable only if directed by Carrier Control Systems Support. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 38: Device

    Critical Equipment 128–191 Urgent 192–255 Normal Priority of Off-Normal BACnet priority for Alarms. Priority of Fault BACnet priority for Fault messages. Priority of Normal BACnet priority for Return-to-normal messages. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 39: Calendars

    Uncheck the types of alarms you do not want the recipient to get. Calendars Calendars are provided in the driver for BACnet compatibility only. Instead, use the Schedules feature in the i-Vu® interface. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 40: Common Alarms

    In a typical i-Vu® system, the Notification Class is 1; however, if needed, you can associate a different notification class with the alarm. See Notification Classes (page 34) to set up alarm delivery options for a specific Notification Class. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 41: Specific Events

    For the input to use the translation table, go to the control program's Properties page > I/O Points tab. Click the analog input in the Name column. On the Details tab, set Sensor Type (Scaling Method) to Non-Linear, Custom Table #__. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 42: Bacnet Controller Properties

    0:00 to have the controller use the Next settings as soon as the controller can communicate with the Next Default Gateway Address. See "To remotely change a controller's IP address" in i-Vu® Help for more information on using this feature. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 43: Bacnet Firewall

    TV-UCXP683T. Whitelist Rejections (if BACnet Firewall (page 39) is enabled)—Messages blocked by the BACnet Firewall because the IP address that sent the message was not in the whitelist. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 44: Network Diagnostics - Packet Capture

    FIFO errors, frame errors, length errors, missed errors, and overrun errors. Transmit Errors (total)—All errors related to transmitted packets such as aborted errors, carrier errors, dropped errors, FIFO errors, heartbeat errors, and window errors. Dropped Packets—Packets dropped by the TV-UCXP683T's Ethernet interface.
  • Page 45: Act Net Bus

    Serial Number The serial number of the Act Net device. This number is printed on a label on the device. Device Status Displays the current status of the device TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 46 When a device that does not have an address is found on the bus, an unused address in automatically assigned. You can select a different address in the New Device Address field, if needed. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 47: Communication Status

    Modbus Serial, Modbus TCP/IP, and Modbus Error Definitions pages If the controller will be used with Modbus devices, see the Modbus Integration Guide for information on using these pages. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 48: Flow Calibration Archive

    Enable Trend Historian Archives trend data to the system database. Store Trends Now Writes all trend data in the controller to the system database without having to enable trend historian. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 49 System Options > System Settings > General tab. Select the second option to set a value for this trend only. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 50: To Set Up The Controller Through The Service Port

    You can communicate with the TV-UCXP683T through a web browser by connecting a computer to the controller's Service Port using either the Carrier wireless service adapter or a USB cable. NOTE You cannot access the Service port by plugging an Ethernet cable into Eth0 or Eth1.
  • Page 51: Device Tab

    BACnet Object Device Instance Autogenerated—(Default) The Device Instance is automatically set to a number using the IP Address, Subnet information, and the Carrier vendor ID 16. Assigned—Lets you enter a specific number that is unique on the BACnet network. Device Name Autogenerated—(Default) The Device Name is automatically set as the word...
  • Page 52: Bacnet Tab

    Export the Local Devices that are present in the table (limited to 256) to a .csv file. • Set a device's Mode, Address, and Location. • Assign IP addresses to multiple devices at one time. • Prompt an LED to blink on a device. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 53 Click Discover to populate the table with your i-Vu® XT or TruVu™ devices that are on a single network communicating with the connected i-Vu® XT or TruVu™ controller. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 54 To resolve a mismatch, select the device(s) by clicking the Select checkbox and then clicking the Resolve button. The subnet mask and default gateway addresses of the selected devices change to match the connected controller. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 55 NOTE If a device's IP address is the loopback address (127.0.0.1), it is considered unconfigured and unlocked. The IP address, subnet mask, and default gateway fields are blank in the Ports and Local Network tabs. You can configure it in the Local Devices table. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 56: To Communicate Through The Bacnet/Service Port Network

    65535 - searches for an available network number from 65531 to 65534. If any of these numbers are ○ not available, you will have to assign a network number and enter it. 13 Click Apply. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 57 18 On the navigation tree, right-click the controller that you are connected to and select Module Status. If a Modstat report appears, the i-Vu® application is communicating with the controller. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 58: To Communicate Locally Through The Rnet Port

    Connect the other end of the 3-wire cable to the TV-UCXP683T's Rnet port as shown in the drawing above in step 1. Connect the 3-pin connector to the portion of the USB link kit shown in the drawing below, then connect the USB connector to the computer. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 59: To Set Up A Local Access Connection In The I-Vu® Interface

    14 Type rnet here in the dialog box, then click OK. 15 On the Properties page, click Module Status. If a Modstat report appears, the i-Vu® application is communicating with the controller. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 60: Troubleshooting

    Troubleshooting Troubleshooting If you have problems mounting, wiring, or addressing the TV-UCXP683T, contact Carrier Control Systems Support. LEDs Net (Network Status) Tricolor LED Color Pattern Condition Message in Module Possible Solutions Status • Connect Ethernet Cable Ethernet connection problem No Ethernet Link •...
  • Page 61 Slow blink Linux (operating system) is No action required Blue starting up Fast blink Linux is running but it could not Download driver Blue start the firmware application TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 62: To Configure Custom Prog Led

    The pulse pattern repeats after a 2-second delay LED will blink the number of times given in the BAO with ON pulse 0.5 seconds and OFF pulse 0.5 seconds. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 63: To Get A Module Status Report

    Click the Name of any input or output whose name is red (indicates an error) to open its dialog box. On the Details tab, scroll down to see the Reliability field under BACnet Configuration. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 64: To Get A Device Log

    To get a Device Log If Carrier Control Systems Support instructs you to get the controller's Device Log containing diagnostic information for troubleshooting: Select the TV-UCXP683T in the i-Vu® navigation tree.
  • Page 65: To Get The Tv-Ucxp683T's Serial Number

    Use the same polarity for all of them. You can purchase the 3 A, fast-acting, 5mm x 20mm glass fuse from Littelfuse, mfr part #0235003.HXP. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 66: To Revert To Default Settings

    We highly recommend that you revert the defaults settings only under the guidance of Carrier Control Systems Support. To erase volatile memory data and restore factory default configuration settings, use AppLoader to download the appropriate clipping.
  • Page 67: To Take The Tv-Ucxp683T Out Of Service

    UCXP683T by shutting down communication from the TV-UCXP683T to the i-Vu® application. When Out of Service, i-Vu® no longer communicates properties, colors, trends, etc. On the i-Vu® navigation tree, select the TV-UCXP683T. On the Properties page, check Out of Service. Click Accept. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 68: Compliance

    Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. BACnet Compliance Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet ® International. BTL is a registered trademark of BACnet International. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 69: Appendix - Module Status Field Descriptions

    Gives the current status of the controller's networks. See LEDs (page 56) for all possible conditions. System error message history High-severity errors since the last memory download. Shows the most recent 10 messages. See NOTE below this table. TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 70 See NOTE below this table. Core and Base board hardware Gives the following information about the controller's boards: • Type and board numbers that are used internally by Carrier. • The manufacture date and serial number. Number of BACnet Objects The number of BACnet objects that were created in the device and the number of those objects that are network visible.
  • Page 71: Document Revision History

    Changed Real time clock specification to "up to 3 days" from "at X-PM-BM-O least 3 days". Changed EU RoHS compliance code. Rephrased Act Net addresses to list fixed addresses. * For internal use only TruVu™ UCXP683T CARRIER CORPORATION ©2022 Installation and Start-up Guide All rights reserved...
  • Page 73 Carrier ©2022 · Catalog No. 11-808-851-01 · 5/10/2022...