Addressing the TV-PSM

To set the Port S1 address and baud rate

The address should be in one of the following ranges based on the port's use.
Port address
For ARCNET, the range is 1 to 254.
For MS/TP, the range is 0 to 127.
For Modbus, the range is 1 to 247.
For MS/TP, set up autobaud or the port's baud rate
On the controller setup BACnet tab under Port S1, select the MSTP Baud Rate or select Yes for MSTP
1
Autobaud. The default is 76,800 bps.
NOTES
See To set up autobaud (page 17) for details.
If not using autobaud, enter the identical baud rate for all devices on the same MS/TP network segment.
Click Save.
2
Modbus
For Modbus, see the Modbus Integration Guide.

To set the Port S2 address and baud rate

For MS/TP, set up autobaud or the port's baud rate
On the controller setup BACnet tab under Port S2, type the address in the MSTP Address field. The address
1
must be in the range 0 to 127.
Select the MSTP Baud Rate or select Yes for MSTP Autobaud. The default is 76,800 bps.
2
NOTES
See To set up autobaud (page 17) for details.
If not using autobaud, enter the same baud rate for all devices on the MS/TP network.
Click Save.
3
Modbus
For Modbus, see the Modbus Integration Guide.
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
20
©2022 Carrier.
All rights reserved.