Device

The Device page provides the following information plus the items described in the table below:
BACnet device object properties for the TV-PSM
The character sets supported by this device for BACnet communication
Configuration
BACnet System Status
The following fields refer to all networks over which the TV-PSM communicates.
APDU Timeout
APDU Segment Timeout
Number of APDU Retries
Controller Clock
Time Broadcaster will
synchronize time every ____
Time Synchronization
Recipients
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
The current state of the controller:
Operational
Download in Progress
Download Required
Backup in Progress
Non-Operational
How many milliseconds the device will wait before resending a message if no
response is received.
How many milliseconds the device will wait before resending a message segment
if no response is received.
The number of times the device will resend a message.
If you have third-party BACnet devices on one of the router's networks, you can
have the router send a BACnet time sync to those devices at the interval you
define in this field.
To define third-party BACnet devices as Time Synchronization Recipients:
Click Add.
1
Select Device ID, Address, Local Broadcaster, or Global Broadcaster in the
2
Recipient Type field.
If you selected Device ID or Address, enter the information.
3
Click Accept.
4