Device tab

BACnet Object
Device Instance
Device Name
Device Location
Device Description
Configuration
APDU Timeout
APDU Segment Timeout
APDU Retries
Controller Information
Clear Counts/Logs
Data Backup and Restore
Backup
Restore
Network Factory Defaults
Reset
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
Autogenerated—(Default) The Device ID is automatically set to a number equal to
the (IP network number) x 100 + rotary switch address.
Assigned—Lets you enter a specific number that is unique on the BACnet network.
Autogenerated—(Default) The Device Name is automatically set as the word
device + the Device Instance. For example, device2423911.
Assigned—Lets you enter a specific name that is unique on the BACnet network.
You can enter an intuitive location for the device in the i-Vu® interface.
You can enter an intuitive description for the device in the i-Vu® interface.
How many milliseconds the device will wait before resending a message if no
response is received.
How many milliseconds the device will wait before resending a message segment
if no response is received.
The number of times the device will resend a message.
Clears Reset counters and the three message history fields from the Module
Status.
Displays time of the last backup. Click button to backup the controller's control
programs, properties, and schedules.
Displays time of the last restore. Click button to restore the most recent backup
of the controller's control programs, properties, and schedules.
Resets the controller to network factory default settings.
43
To set up the controller through the Service Port
All rights reserved.