To Attach Truvu Mpc I/O Expanders - Carrier TruVu ChillerVu Installation And Startup Manual

Plant controller
Table of Contents

Advertisement

To attach TruVu MPC I/O expanders

A TruVu
TM
MPC I/O expander can be directly-connected to the TV-PSM's I/O bus edge connector or wired to the TV-
PSM's I/O Bus port.
To connect the TruVu
NOTE The following instructions assume that the controller is already mounted either on a DIN rail or using
screws.
Turn off the TV-PSM's power.
1
Remove the plastic protective cap from the TV-PSM's I/O bus edge connector and the expander's edge
2
connector. Squeeze the plastic tabs to pull the cap off.
WARNING This connector provides power and communication. To prevent risk of shock, do not touch
the bare edge connector if the controller's power is on.
DIN rail mounting only—Push down and pull out the expander's center tabs shown below.
3
Slide the expander's left edge connector down onto the TV-PSM's edge connector.
4
Do one of the following:
5
DIN rail mounting—Push in the expander's center tabs towards the expander until you hear them click.
Pull gently on the expander to verify that it is locked to the DIN rail.
Screw mounting—Insert #6 screws through the expander's mounting holes.
Optional: If using DC power, you may connect additional TruVu
6
described above. See the diagrams in TruVu
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
MPC I/O expander to the I/O bus edge connector
TM
TM
TM
MPC I/O expanders in the same manner
MPC I/O expander configurations (page 9).
13
To attach I/O expanders