BACnet tab

IP Port
BACnet Network Number
BACnet UDP Port
Enable NAT Routing
BACnet Secondary IP Net
Number
BACnet Secondary UDP Port
Ethernet Port
BACnet Network Number
Port S1
Active Protocol
Address
ARCNET Baud Rate
BACnet Network Number
Port S2
Active Protocol
Home Network
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
Disable Routing—Select if the IP port is not used.
Autogenerated—The BACnet/IP network number is automatically set to 1600.
Assigned—Lets you enter a specific number.
The port that the i-Vu® application will use for BACnet communication.
For future use.
Check if the TV-PSM is behind a NAT router (firewall).
If the TV-PSM has two BACnet/IP networks communicating on the Gig-E port, enter the
second IP network number in this field.
If the TV-PSM is behind a NAT router and there is a second network with BACnet/IP
devices behind the NAT router, enter the second network number in this field to
logically connect the TV-PSM to the devices on the second network.
BACnet
router
R
C
Sec ondary I P
Controller
network
If the TV-PSM has two BACnet/IP networks communicating on the Gig-E port, enter the
port number that the i-Vu® application will use for BACnet communication. This port
must be different than the BACnet UDP Port.
Specify a number for the BACnet/Ethernet network or set to 0 if the port is not used.
Indicates status of the controller's Port S1 rotary switch.
0=Disabled
1=MS/TP
2=ARCNET
3=Modbus
The address that is set on the three rotary switches. See To set the Port S1 address
and baud rate (page 20).
156000
Select:
Disable Routing if Port S1 is not used.
Autogenerated to have the network number for Port S1 automatically set to a number
equal to ((IP network number + rotary switch address) x 10).
Assigned to enter a specific number.
Shows one of the following:
Modbus if enabled on the Modbus tab
BACnet/MSTP if you enter a BACnet Network Number below for an MS/TP network
Disabled if neither of the above have been done
This is typically the network that is communicating with the building automation
system's application. This sets the BACnet Address of the Device object.
45