Troubleshooting
Troubleshooting
If you have problems mounting, wiring, or addressing the TV-PSM, contact Carrier Control Systems Support.
LEDs
Net (Network Status) Tricolor LED
Color
Pattern
Condition
On
Ethernet connection problem
Red
1 blink
One of the following BACnet/IP
Red
(Ethernet) DLL reporting issue:
•
•
2 blink
Current default IP address does not
Red
match the current rotary switch setting
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
Unable to create tasks
Unable to open socket for BACnet
port
Message in Module
Status
No Ethernet Link
BACnet/IP error
Default IP address
mismatch
48
Possible Solutions
•
Connect Ethernet Cable
•
Check other network
components
Cycle power
•
Use the controller setup
Ports tab to set the IP
address
•
Cycle power to accept new
IP address
•
Change rotary switches to
match current default IP
address