Troubleshooting

Troubleshooting
If you have problems mounting, wiring, or addressing the TV-PSM, contact Carrier Control Systems Support.

LEDs

Net (Network Status) Tricolor LED
Color
Pattern
Condition
On
Ethernet connection problem
Red
1 blink
One of the following BACnet/IP
Red
(Ethernet) DLL reporting issue:
2 blink
Current default IP address does not
Red
match the current rotary switch setting
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
Unable to create tasks
Unable to open socket for BACnet
port
Message in Module
Status
No Ethernet Link
BACnet/IP error
Default IP address
mismatch
48
Possible Solutions
Connect Ethernet Cable
Check other network
components
Cycle power
Use the controller setup
Ports tab to set the IP
address
Cycle power to accept new
IP address
Change rotary switches to
match current default IP
address