Thermal Restriction Matrix - Dell PowerEdge R760 Installation And Service Manual

Table of Contents

Advertisement

Table 28. Particulate contamination specifications
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Walk-Up Edge Data Center or Cabinet (sealed, closed
loop environment)
Table 29. Gaseous contamination specifications
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate

Thermal restriction matrix

Table 30. Processor and heat sink matrix
Heat sink
STD HSK
2U HPR HSK
L-type HSK
NOTE:
All GPU/FGPA cards require 1U L-type HSK and GPU shroud.
Table 31. Label reference
Label
STD
HPR (Silver)
40
Technical specifications
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit
NOTE:
This condition applies to data center environments only. Air
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles
NOTE:
This condition applies to data center and non-data center
environments.
● Air must be free of corrosive dust
● Residual dust present in the air must have a deliquescent point less
than 60% relative humidity
NOTE:
This condition applies to data center and non-data center
environments.
Filtration is not required for cabinets that are anticipated to be opened
6 times or less per year. Class 8 per ISO 1466-1 filtration as defined
above is required otherwise
NOTE:
In environments commonly above ISA-71 Class G1 or that
may have known challenges, special filters may be required.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
<200 Å/month as defined by ANSI/ISA71.04-2013
Processor TDP
≤ 165 W (supports only 2.5-inch drives and non-GPU
configuration)
125 W–250 W (supports 3.5-inch drives and non-GPU
configuration)
165 W–350 W (supports 2.5-inch drives and non-GPU
configuration)
Supports all GPU/FPGA configurations
Description
Standard
High performance Silver (HPR) fan