• Ethernet:
Connect the charging station to the SICHARGE UC MastHood, MastPanto or Dispenser
using an Ethernet cable.
Specifications for laying of cables:
– Low-voltage and DC cables must be installed shielded from the Ethernet cable.
– Separate cable routing for low-voltage and DC cables (min. 20 cm).
– Lay the Ethernet cable close to earthed cabinet components.
– Ethernet cables, low-voltage and DC cables may only cross each other at 90° angles.
– Connect the shield of the Ethernet cable to the protective earthing at both cable ends.
5.2.7
Bumper
To protect the charging station against contact by vehicles, install a bumper
①
②
③
Figure 5-7 Example: Correct position of the bumper and charging station
Plan for bumpers based on the dimensions of the vehicles used. The bumper must stop the
vehicle before the vehicle overhang touches the charging station
interfere with the opening of the charging station's cabinet door.
SICHARGE UC 150
Operating Instructions, 02/2023, A5E50068475-AB
Bumper
Safety clearance
Charging station
Preparing for use
5.2 Location planning
①
.
③
. The bumper must not